Pocket RefeRence Guide — 25
(cont’d)
6. Find Wire Size for two conductors:

PAR 000 CU
WIRE SIZE
7. Exit Free Air Mode and Clear:
 60 Cu 0.
Finding Derated Wire Size
A circuit was built with 60°C Copper
wire connecting a 47,650 VA load
to a 240 Volt, 3Ø source. Ambient
Temperature is 50°C. What is the
Derated Wire Size required if eight
current-carrying THHN wires are
installed in the raceway?
KEYSTROKE DISPLAY

0.
1. Set to 3-Phase:
(3Ø)
3 PH
2. Set to 60º C:
(60º)
60
3 PH
3. Set to Copper (if necessary):
(Cu/Al)
60 Cu
3 PH
4. Enter Volt-Amps:

VA 47,650.
5. Enter Volts:

VOLT 240.
6. Find Amps:
AMPS 114.62808.