User's GUide — 33
KEYSTROKE DISPLAY
2. Set to 90º C:
(90º)
1 Ø 90 1 PH
3. Set to Copper (if necessary):
(Cu/Al)
1 Ø 90 Cu 1 PH
4. Enter VA:

VA 47,700.
5. Enter Volts:

VOLT 240.
6. Find Amps:
AMPS 198.75
7. Find Wire Size:
AWG 000 CU WIRE SIZE
8. Change Ambient temperature:
(Ambº)
1Ø 90 Cu Amb AMB° 20. ºC
9. Find adjusted Wire Size:
AWG 00 CU WIRE SIZE
10. Display Wire Ampacity:
ØØ* 210.6 WIRE A
* The Wire Size will be shown in the upper left area of the display when
displaying the Wire Ampacity rating.
11. Display CMIL:
CMIL 133,100. WIRE
12. Display NEC table:
NEC 310.15.b.16
13. Reset Ambient Temperature and Clear:

1Ø 90 Cu 0.